Bitmain
Bitmain ANTPDU PW12V1
- Input breaker
- 100 A 3-pole
- Input voltage (V)
- 346-480 AC, 3P+N+PE
- Frequency (Hz)
- 50/60
$320
Fits 2 models
Power distribution units for racks of miners, with input voltage and current, outlets and breaker protection as published.
Main specs, the models each one fits, and price or quote.
Bitmain
$320
Fits 2 models
Raptor Power Systems
Price on request
Raptor Power Systems
Price on request
Match the PDU’s input plug and voltage to your supply, and count its outlets against the machines it will feed.
Add up the draw of every miner on the PDU and keep the total under the circuit rating, with margin.
Metered or switched outlets let you read each machine’s draw and restart one remotely.
Divide the watts on each miner’s page by your voltage to get its amps: 3,500 W at 240 V is 14.6 A. Add up the machines on each bank of outlets and keep each bank, and the PDU as a whole, within its continuous rating.
On a three-phase supply of 415 V between phases, each outlet sees about 240 V between one phase and neutral, and each phase carries a third of the machines. Spread them evenly so no phase carries more than its share.
Leave room behind the rack for cords to bend, keep the PDU out of the hot exhaust, and label each outlet with its machine, so a breaker that trips points at one circuit instead of the whole rack.
Check the part number on the part you are replacing; revisions within one model can differ.
Prices include delivery to your door. Your invoice shows every line.
Need more than one, or a part we do not list?
Send the model and the part number. A person replies with price, stock and a dispatch date.
Request a quote Repair servicePrices listed here start at $320 with delivery included.
As many as its outlets and its current rating allow: add each miner’s draw at your voltage and keep the total below the rating.
For large fleets it is common, and three-phase PDUs spread the load across the phases. Small sites run on single phase.
A miner is a continuous load, so in the United States its circuit is loaded to no more than 80% of the breaker. A 30 A breaker carries 24 A all day, which at 240 V is 5,760 W; a 50 A breaker carries 40 A, or 9,600 W.
Look at the inlet on the machine’s power supply. C13 outlets are rated for less current than C19, so larger power supplies use C19 or a fixed connector. A supply with two inlets needs both connected.
No. A rack PDU is built for a continuous load, takes a higher voltage and a locking plug or fixed wiring, and protects its outlets in banks with their own breakers.