ANT COLD STORAGE (ACS)

For ANTSPACE hydro sites that want a store of cooling to cover several hours of high heat load.

Heat rejection
100 kW
Rated power (kW)
40
Maximum power
80 kW

About the ANT COLD STORAGE (ACS)

The Bitmain ANT COLD STORAGE (ACS) is a chilled-water thermal storage unit in a 40 ft container. It works alongside Bitmain's ANTSPACE HW7, HD5 and HK3 hydro containers: it stores cooling capacity and hands it back to the loop when the site needs it.

The tank holds 48 m³ of pure or deionised water and stores 8 GJ of cold, about 1.91 million kcal. That is typically six hours of cooling supply. It uses no water while running, has an EER of 2.5 and rejects up to 100 kW of heat. Rated power is 40 kW, with a maximum of 80 kW.

Power input is 380 V, 50 Hz or 480 V, 60 Hz, three-phase with neutral and earth, through a 250 A main breaker and 95 mm² cable. The unit measures 12,192 x 2,438 x 2,896 mm, weighs 11 t, runs from -20 to 55 °C and up to 2,000 m, and is rated at 70 dB. It carries CE, UL, CSA and CCS certification.

What it holds

Capacity and performance

Energy efficiency ratio
2.50
Maximum power
80 kW
Certifications
CE, UL, CCS, CSA
Rated power (kW)
40
Storage temperature
5–45 C
Cold storage (GJ)
8

What your site needs

Power, cooling and space to plan before it arrives.

  • Power supply

    Input options
    380 V/50 Hz 3P/N/PE; 480 V/60 Hz 3P/N/PE
    Voltage (V)
    380–480
    Phase
    Three phase
    Frequency (Hz)
    50/60
  • Cooling loop

    Coolant volume
    48,000 L
    Heat rejection
    100 kW
    Cooling duration (h)
    6
    Fluid
    pure water / deionized water
  • Space and handling

    Maximum altitude (m)
    2,000
    Noise (dB)
    70
    Dimensions (mm)
    12,192 × 2,438 × 2,896
    Weight (kg)
    11,000
    Operating temperature (°C)
    −20 to 55
    Operating humidity (%)
    10–90

Where it fits

What this kind of equipment does on a mining site.

  • Carries heat out of hydro loops

    Pairs with hydro racks or hydro containers and moves the heat from the coolant into the outside air.

  • Sized by the heat it rejects

    Choose it by the kilowatts of heat it must remove, and match it to the racks or containers it serves.

  • Built for outdoor duty

    Fans and coils sit outside, so plan clear space around the unit for the air to move.

In the box

  • One ANT COLD STORAGE (ACS)

Warranty and returns

  • 365-day manufacturer warranty
  • Something wrong? Write to us and we open the claim with the maker.
  • Cancel for a full refund until we process your order. After that it is final; faulty or wrong items are put right.

ANT COLD STORAGE (ACS): questions buyers ask

Ask us something else
Which containers does the ACS work with?

It is listed for the ANTSPACE HW7, HD5 and HK3 hydro containers.

What water goes in the tank?

Pure or deionised water, 48 m³ in total. It does not consume water during operation.

How long can it supply cooling?

Typically about six hours, from a stored capacity of 8 GJ.

What power connection does it need?

Three-phase 380 V, 50 Hz or 480 V, 60 Hz with neutral and earth, a 250 A main breaker and 95 mm² input cable.

Is delivery included in the price of the ANT COLD STORAGE (ACS)?

Yes. The price shown includes delivery. We confirm the dispatch date and freight route in writing with your order.

Can I get a quote for several ANT COLD STORAGE (ACS) units?

Yes. Ask for a quote with the quantity and your site’s location, and a person replies with price, stock and a dispatch date.

How do I know the ANT COLD STORAGE (ACS) fits my setup?

Send us your miner models, power supply and cooling. We check the fit against the specifications on this page before you order.

More in dry coolers

  • In stock

    Lian Li

    Lian Li Hydro Cooling Radiator 12 kW

    Heat rejection
    12 kW

    $809

    View specs
  • Lian Li

    Lian Li Hydro Cooling Radiator 4 kW

    Heat rejection
    4 kW

    Price on request

    View specs
  • Bitmain

    ANTRACK AR31 External Dry Cooler

    Heat rejection
    200 kW
    Fans
    2 x 4.1 kW at 380 V; 2 x 4.7 kW at…
    Current
    15.80 A

    Price on request

    View specs
  • Bitmain

    ANTSPACE HD5 V1 Dry Cooling Tower

    Heat rejection
    1,500 kW
    Interface
    DN100 PN16
    Tower power, maximum (kW)
    80

    Price on request

    View specs
  • Bitmain

    ANTSPACE HK3 V7 Dry Tower

    Heat rejection
    650 kW
    Interface
    DN125 tower, DN100 heating/PHE
    Tower power (kW)
    20–32

    Price on request

    View specs
  • Bitmain

    ANTSPACE HW5 V1 Dry-Wet Tower

    Heat rejection
    1,200 kW
    Interfaces
    DN40 supply, DN65 drain
    Tower power (kW)
    14–28

    Price on request

    View specs

Skip the build: host with us in Texas

A site needs transformers, cooling, a power contract and staff. Hosting with us starts at $0.074 per kWh for 10–49 machines, metered per machine, with your own pool account and wallet.