ANTSPACE HK3 V6 Dry-Wet Tower

For HK3 V6 sites that want one tower to carry close to a full container load and can supply spray water.

Heat rejection
1,000 kW
Interfaces
DN125 container, DN40 water supply, DN65 drain
Tower power (kW)
14–28

About the ANTSPACE HK3 V6 Dry-Wet Tower

The ANTSPACE HK3 V6 Dry-Wet Tower is a hybrid cooling tower that Bitmain paired with the HK3 V6 hydro container. It runs dry in cool weather and sprays water over the coils in wet mode when it needs more capacity. We list it at 1,000 kW of heat rejection.

The tower itself draws 14 to 28 kW. It connects to the container over DN125, takes water through a DN40 supply and drains through DN65. Noise is listed at 70 dBA measured at 15 m and 25 C.

At 1,000 kW it can carry close to a full HK3 V6 load from one tower, where the dry-only V6 tower is listed at 500 kW. The trade-off is a water supply, a drain and water treatment for the spray circuit. The model is now legacy; we keep this page for sites still running it.

What your site needs

Power, cooling and space to plan before it arrives.

  • Power supply

    Interfaces
    DN125 container, DN40 water supply, DN65 drain
  • Cooling loop

    Tower power (kW)
    14–28
    Heat rejection
    1,000 kW
  • Space and handling

    Noise (dB)
    70
    Weight (kg)
    7,000

Where it fits

What this kind of equipment does on a mining site.

  • Carries heat out of hydro loops

    Pairs with hydro racks or hydro containers and moves the heat from the coolant into the outside air.

  • Sized by the heat it rejects

    Choose it by the kilowatts of heat it must remove, and match it to the racks or containers it serves.

  • Built for outdoor duty

    Fans and coils sit outside, so plan clear space around the unit for the air to move.

In the box

  • One ANTSPACE HK3 V6 Dry-Wet Tower

Warranty and returns

  • 365-day manufacturer warranty
  • Something wrong? Write to us and we open the claim with the maker.
  • Cancel for a full refund until we process your order. After that it is final; faulty or wrong items are put right.

ANTSPACE HK3 V6 Dry-Wet Tower: questions buyers ask

Ask us something else
How much heat does it reject?

We list 1,000 kW.

How much power does the tower itself use?

14 to 28 kW.

How loud is it?

70 dBA at 15 m, measured at 25 C.

What connections does it need?

DN125 to the container, a DN40 water supply and a DN65 drain.

How is it different from the V6 Dry Tower?

The dry-only tower is listed at 500 kW and uses no spray water. The dry-wet tower doubles that to 1,000 kW but needs a water supply and drain.

Is delivery included in the price of the ANTSPACE HK3 V6 Dry-Wet Tower?

Yes. The price shown includes delivery. We confirm the dispatch date and freight route in writing with your order.

Can I get a quote for several ANTSPACE HK3 V6 Dry-Wet Tower units?

Yes. Ask for a quote with the quantity and your site’s location, and a person replies with price, stock and a dispatch date.

How do I know the ANTSPACE HK3 V6 Dry-Wet Tower fits my setup?

Send us your miner models, power supply and cooling. We check the fit against the specifications on this page before you order.

More in dry coolers

  • In stock

    Bitmain

    ANT COLD STORAGE (ACS)

    Heat rejection
    100 kW
    Rated power (kW)
    40
    Maximum power
    80 kW

    $81,600

    View specs
  • In stock

    Lian Li

    Lian Li Hydro Cooling Radiator 12 kW

    Heat rejection
    12 kW

    $809

    View specs
  • Lian Li

    Lian Li Hydro Cooling Radiator 4 kW

    Heat rejection
    4 kW

    Price on request

    View specs
  • Bitmain

    ANTRACK AR31 External Dry Cooler

    Heat rejection
    200 kW
    Fans
    2 x 4.1 kW at 380 V; 2 x 4.7 kW at…
    Current
    15.80 A

    Price on request

    View specs
  • Bitmain

    ANTSPACE HD5 V1 Dry Cooling Tower

    Heat rejection
    1,500 kW
    Interface
    DN100 PN16
    Tower power, maximum (kW)
    80

    Price on request

    View specs
  • Bitmain

    ANTSPACE HK3 V7 Dry Tower

    Heat rejection
    650 kW
    Interface
    DN125 tower, DN100 heating/PHE
    Tower power (kW)
    20–32

    Price on request

    View specs

Skip the build: host with us in Texas