Cooling
Hydro vs air vs immersion cooling: which one fits your site
Hydro vs air vs immersion cooling for ASIC miners: what each needs on site, noise, heat, upkeep, and which suits a home, a container or a farm.
Short answer
Air cooling needs only a circuit and a way out for hot air, so it suits a first machine and most small sites. Hydro needs three-phase power, a closed water loop and a cooler outdoors, and in return gives the most hashrate per machine and almost silent rows. Immersion needs a tank of dielectric fluid and suits dusty, hot or noise-limited sites and sealed containers.
- S21 XP hashrate
- 270 TH/s
- S21 XP power
- 3,645 W
- S21 XP efficiency
- 13.5 J/TH
- S21 XP highest supply voltage
- 277 V
Every watt a miner draws comes out again as heat. The cooling type only decides what carries that heat away: air, water in a plate, or a bath of oil. That choice then decides your wiring, your noise and who can service the machine, so it is worth making before you pick a model.
Hydro vs air vs immersion cooling: one miner, three versions
Bitmain sells the Antminer S21 XP in all three forms, which makes the comparison unusually clean. These are the specs in our catalog on 24 November 2026.
| S21 XP, air | S21 XP Hyd | S21 XP Imm | |
|---|---|---|---|
| Hashrate | 270 TH/s | 473 TH/s | 300 TH/s |
| Power | 3,645 W | 5,676 W | 4,050 W |
| Efficiency | 13.5 J/TH | 12 J/TH | 13.5 J/TH |
| Supply | 220 to 277 V, single phase | 380 to 415 V, three phase | 380 to 415 V, three phase |
| Net weight | 18.7 kg | 13.8 kg | 16.8 kg |
| Cooled by | Fans and room air | Water or antifreeze in cold plates | Immersion oil |
| Allowed intake | −20 to 45 °C air | 20 to 50 °C coolant | 20 to 50 °C oil |
| Noise at the machine | 76 dB | No fans | No fans |
Two things stand out. Water carries heat well enough that the hydro version runs far more hashrate and still uses 1.5 joules less per terahash. And only the air version plugs into an ordinary 240 V circuit. The other two ask for three-phase power, which settles the question in most homes.
What does an air-cooled site need?
The list is short: a dedicated circuit, a network cable, and two separate paths for air, cool in and hot out.
How much air? MicroBT's manual for the WhatsMiner M6 series gives 350 CFM for the air-cooled M60S+ and a working range of −5 to 35 °C. At 3,400 W, that much air leaves the machine about 17 °C warmer than it came in. Let it find its way back to the intake and the next pass starts 17 °C higher. Most overheating complaints are this, not a fault.
So the room has to swap its air all the time, summer included. In a shed that means an intake low on one side and an exhaust on the other, with the exhaust ducted so it cannot loop around. Filters on the intake keep dust off the heatsinks and have to be changed before they choke the flow.
What does a hydro site need?
A hydro miner is a box with two hoses. Everything else is plumbing you provide:
- A closed loop, with a pump, a filter, a pressure gauge and an expansion vessel.
- A heat exchanger or dry cooler outdoors, sized for the machine's full power on the hottest day.
- The right liquid. MicroBT asks for pure or distilled water with a corrosion inhibitor and antifreeze, at a pH of 7 to 8.7, a rated flow of 10 L/min for a 10 kW-class hydro unit and no more than 400 kPa. Tap water scales and corrodes.
- Three-phase power, 380 to 480 V depending on the maker.
- A plan for frost and for leaks. Antifreeze handles the first; drip trays, valves on each machine and a leak sensor handle the second.
You do not have to design it yourself. A cabinet such as the Antrack AR21 holds four standard hydro Antminers, removes 24 kW, has the pump and plate heat exchanger built in, draws 450 W for itself and is rated at 60 dBA at one metre. You connect power and an outdoor cooler.
The other advantage is the temperature of the water coming back. MicroBT lists hydro models whose outlet reaches 70 °C and one that reaches 80 °C. That is hot enough for radiators, a greenhouse or domestic hot water, which is hard to do with warm air.
What does an immersion site need?
A tank, the fluid, a pump, and a cooler outdoors. The machine has no fans and sits fully under the surface. How immersion works covers the two kinds of fluid; in the single-phase kind, the one these machines use, the oil never boils.
MicroBT's manual for the WhatsMiner M66S family names the fluids (Shell S5 X and S3 X), asks for an inlet between 25 and 55 °C held to within 2 °C, a rated flow of 24 L/min and 380 to 480 V.
Sizes run from one machine to a thousand kilowatts. The Fog Hashing C1 takes a single miner, holds 40 L of coolant, moves 6 kW outdoors and is rated at 45 dB. At the other end, the Antspace MD5 container holds 160 immersion Antminers at 1,000 kW with a PUE of 1.06, so the cooling adds six percent on top of the machines.
Plan the floor as well. Fluid is heavy, and the MD5 weighs 18.5 t in operation before its cooler, which adds about another 12.8 t.
Which is quieter?
Put your ear to the machine and hydro and immersion win outright, because there is nothing to spin. Put your ear to the site and the answer is about the cooler: a dry cooler has large slow fans outdoors, and you choose where it stands.
An air-cooled S21 XP is rated at 76 dB. Two of them side by side add about 3 dB, ten add about 10 dB. A garage with a solid door copes with one. A bedroom wall does not.
How much work is the upkeep?
| Air | Hydro | Immersion | |
|---|---|---|---|
| Every week | Look at temperatures and fan speeds | Look at flow, pressure and temperatures | Look at fluid level and temperatures |
| Every month | Clean or change intake filters | Check for drips, clean the strainer | Check the filter and the pump |
| Every quarter | Blow out dust, listen to fans | Test pH and inhibitor, top up | Top up fluid, test it if it darkens |
| Swap a machine | Minutes, two plugs | Close two valves, drain the hoses | Lift, drip, drain, clean hands |
| What wears out | Fans | Pump seals, hoses | Pump, fluid quality |
| Spares to keep | Fans, a power supply | Hoses, clips, coolant | Fluid, filters, gloves |
Intervals are sensible starting points for a clean site, not a maker's schedule. A dusty yard needs filters far more often.
Air has the most small jobs and the easiest ones. Anyone can change a fan. Hydro has fewer jobs, but each one needs the loop understood. Immersion has the least to do in a normal month, and the messiest repair day.
Which suits a home?
Air, nearly always. Either a small machine made for rooms or a full-size one in a garage on its own 240 V circuit. If the noise is the only problem, look at a lower power mode or a quieter model before you change the cooling.
A single-miner tank is the one other route that makes sense, for someone who enjoys the project and has an outside wall for the cooler. Hydro at home is possible where three-phase power and a heating system are already there, because the water can feed the house. It is a plumbing job, so have a heating engineer look at it.
Which suits a container?
All three come as containers, and the choice follows the machines you own.
An air container such as the Antbox N5 V2 is rated at 658 kW with up to 207 slots. Fill it with Antminer S19 XP machines at 3,032 W and all 207 draw 628 kW, inside the limit. With a 3,645 W model the power runs out first, at about 180 machines. It is the cheapest box per slot and the simplest to repair, and it wants dry, clean, mild air.
Hydro and immersion containers cost more and shrug off dust, salt and heat, because no outside air touches a board. If your site is a desert, a coast or a cattle yard, that usually decides it.
Which suits a farm?
At scale the question becomes hashrate per square metre, per technician and per transformer. Hydro leads on the first. Its machines are dense, its rows are quiet enough to talk in, and the heat leaves in a pipe that can be sold or reused. New sites with three-phase power throughout tend to plan for it.
Air keeps its place where land is cheap, the climate is cool and the fleet is mixed, because any air machine from any maker fits any shelf. Immersion fits where noise limits are strict or the air is bad, and where the owner wants to keep one fluid system for many years.
If you would rather not choose at all, hosting moves the question to the site: you pick the machine and we run it.
Can you convert one type to another?
Air to immersion is the common conversion. Fans come off, the firmware has to accept running without them, and the thermal paste and any soft plastics must tolerate the fluid. Ask the maker in writing what it does to the warranty before you start. Buying the immersion version of the same model avoids the question.
Hydro machines stay hydro. Their chips sit behind cold plates, with no fins for air to reach.
Mining income changes daily with difficulty, price and fees. Not financial advice.
Common questions
Is hydro cooling better than air cooling for miners?
It gives more hashrate per machine and less noise, and the efficiency is better: 12 J/TH against 13.5 J/TH for the two versions of the Antminer S21 XP. Air is simpler and cheaper to set up. The better one is the one your site can supply.
Can I run a hydro miner at home?
Only with three-phase power, a closed coolant loop and a cooler outdoors. It is worth looking at if the hot water can feed a heating system you already have.
How loud is an immersion-cooled miner?
The machine itself has no fans. You hear the pump and the outdoor cooler; a single-miner tank we list is rated at 45 dB.
What liquid goes into a hydro miner?
The one its maker names. MicroBT specifies pure or distilled water with a corrosion inhibitor and antifreeze at pH 7 to 8.7. Never tap water.
Does immersion cooling increase hashrate?
The immersion version of a model is often rated higher, 300 TH/s against 270 TH/s for the S21 XP, because fluid holds the chips at a steady temperature. The efficiency of that pair is the same.
Which cooling is best in a dusty place?
Hydro or immersion, because outside air never reaches the boards. With air cooling, plan for filters and frequent cleaning.
Written by Hosting Desk
What hosting costs and how it works