What is immersion cooling?
Immersion cooling submerges miners in a non-conductive liquid that carries heat away to a heat exchanger.
- Fluid
- Non-conductive oil or engineered fluid
- Fans
- Removed
- Heat leaves through
- A heat exchanger and a dry cooler
- Dust and humidity
- Kept off the boards
- Floor
- Must carry the weight of a full tank
What it means in practice
The fans are removed and the fluid absorbs heat directly from the boards, so machines run quieter and at steadier temperatures. That headroom is often used to overclock. The trade-offs are the cost of tanks, fluid, pumps and dry coolers, and more involved maintenance when a machine has to come out of the bath.
Single-phase and two-phase
In single-phase immersion the fluid stays liquid and a pump moves the warm fluid to a heat exchanger. In two-phase the fluid boils on the chips and condenses on a cooled coil above, which can move more heat but needs a sealed tank and a special fluid. Mining sites mostly use single-phase.
What you need
A tank sized for the kilowatts, a dielectric fluid the miner’s maker approves, a pump and heat exchanger, and a dry cooler outside sized for your hottest day. Miners sold as immersion models are made to run without fans; on others the fans come off and the firmware has to allow it.
Sizing the flow
A typical single-phase fluid holds about 1.8 kilojoules per liter for each degree. Divide the heat by that and by the rise you allow, and the pump size appears.
Example figures: a 40 kW tank with a rise of 10 °C needs 40 / (1.8 × 10) ≈ 2.2 liters per second, about 133 liters a minute. Water would need roughly 57 for the same job, since it carries more than twice the heat. That is why the fluid loop is kept short and a heat exchanger hands the heat to water for the trip outdoors.
Preparing a machine for the bath
Fans come off, and the firmware needs to accept that, either through an immersion setting or a small plug that imitates a fan. Labels and stickers peel and block filters, so take them off. Ordinary thermal paste can wash out over time, and some soft plastics and cable jackets harden in oil.
Boards should stand so that warm fluid can rise between the chips. Power supplies either go in the tank, if they are rated for it, or stay dry on top with longer leads.
Weight, floor and safety
Example figures: 1,000 liters of a fluid at 0.8 kilograms per liter weighs 800 kg. With steel and twenty machines the tank passes 1,200 kg on about two square meters. Check the floor before the tank arrives.
Fluids are chosen with a high flash point, but they are still a combustible liquid in quantity. A tray for spills, a lid, a level sensor and the fire rules for your building belong in the plan. Gloves and absorbent mats make daily work pleasant.
Looking after the fluid
A filter takes out dust, solder flux and bits of label. A yearly test shows water content and acidity. Top up what leaves on the boards when a machine is lifted out; hanging it over the tank to drain for an hour saves most of it.
Keep water out. A leak from the heat exchanger is the usual way in, so the fluid side is often run at a slightly higher pressure than the water side.
Repairs take longer than in air. A board has to drain and be cleaned before a technician can solder on it, which is worth counting in the spare parts you keep. Many sites hold a spare machine for each tank and swap it in, then repair at the bench.
When it fits
It fits places where air is hot, dusty or salty, where noise must stay low, and where the heat has a use. Warm fluid at 50 °C is easy to pass on to a building or a greenhouse.
For one or two machines in a mild garage, air is simpler. The tank and dry cooler are shared equipment, so they make sense by the rack.
Worked example
A tank holding 20 machines at 4,000 W each must reject 20 × 4 = 80 kW of heat continuously, so its heat exchanger and dry cooler are sized for at least 80 kW.
Example figures, not live data.
Common mistakes
- Sizing the dry cooler for an average day and not the hottest one.
- Mixing two fluids whose makers have not approved it.
- Leaving the fan check on, so the firmware refuses to start.
Common questions
Can any ASIC miner be immersed?
Many can be converted, but it may end the warranty. Models sold for immersion are built for it; read the maker’s terms for the fluids they allow.
Is immersion cooling quieter?
Yes. The miner’s fans are gone, so what you hear is mostly the pump and the dry cooler.
What fluid is used for immersion mining?
Mostly synthetic or refined oils made for electronics. The miner’s or tank’s maker lists the ones it accepts.
Does immersion raise hashrate?
By itself it keeps temperatures steady. The headroom can be used for a higher power profile.
Can an immersed machine go back to air?
Yes, after cleaning, with fresh thermal paste and fans. Expect some oil to remain in connectors.