PUE (power usage effectiveness)

PUE is a facility's total power use divided by the power that reaches the computing equipment.

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Formula
Site power ÷ power to the machines
Lowest possible
1.0
Standard
ISO/IEC 30134-2
Best read over
Twelve months
Inverse
DCiE, shown as a percentage

What it means in practice

A PUE of 1.0 would mean every kilowatt goes into the machines; anything above that is overhead such as fans, pumps, cooling plant, lighting and transformer losses. The metric came from The Green Grid and is now standardised as ISO/IEC 30134-2. In mining it explains the gap between a site's grid connection and the number of machines it can actually run.

How to read a PUE figure

A PUE of 1.05 means that for every 100 kW reaching the machines the site draws 105 kW. The 5 kW runs fans, pumps and lights and covers losses in transformers and cables. Air-cooled halls with open air flow keep the overhead low; chilled water plants add more.

A figure is only comparable with its season and its meter point. The same site shows a higher PUE on the hottest week of the year than over twelve months.

The fan question

A miner’s own fans are inside the machine, so they count as computing power. A hall’s extract fans are outside it, so they count as overhead. Move the cooling from one side to the other and PUE changes even if the electricity bill does not.

Example figures: an air-cooled machine draws 3,500 W with its fans, in a hall with a PUE of 1.03. The site uses 3,605 W. The same boards in an immersion tank draw 3,300 W, with a PUE of 1.06 for pumps and the dry cooler. The site uses 3,498 W. The higher PUE belongs to the thriftier site.

So compare sites on total watts per terahash when the cooling methods differ. Keep PUE for comparing the same method across seasons.

What sits in the overhead

Transformers lose about one to two percent. Cables and distribution take a little more. Then come extract fans, pumps, dry cooler fans, evaporative pads, lighting, network gear and the office.

An open-sided hall in mild weather needs little of this. A sealed building with chillers needs a lot, which is why office data centers sit well above mining sites.

Overhead in megawatts

Small decimals become large loads. Example figures: 5 MW of miners at a PUE of 1.05 needs 5.25 MW from the grid; at 1.10 it needs 5.5 MW. The gap of 250 kW is 2,190,000 kWh over a year, and it is also room for about 70 more machines of 3.5 kW on the same connection.

That is why a designer chasing the second decimal is doing useful work. It frees capacity that has already been paid for at the substation.

Checking a claim

Ask for the period, the meter points and whether the figure is measured or designed. A design PUE is a drawing. A one-week figure in winter is a good week. A twelve-month figure with named meters is the useful one.

At home you can work out your own. Put one meter on the machine and one on everything that cools it. A 3,200 W miner with a 160 W extract fan runs at 1.05.

Partial figures exist too. A site may quote the PUE of one container or one hall. That is fair as long as it says so, because transformer losses and shared lighting sit outside the box being measured.

Worked example

A site meters 1,050 kW at the utility while its miners draw 1,000 kW, so PUE = 1,050 / 1,000 = 1.05. A 12,000 kW connection at that PUE leaves about 12,000 / 1.05 ≈ 11,429 kW for machines.

Example figures, not live data.

Common mistakes

  • Comparing a design value with a measured one.
  • Multiplying a hosting rate by PUE when the rate is already billed at the machine.
  • Ranking air and immersion sites by PUE alone.

Common questions

What is a good PUE for a mining site?

The closer to 1.0 the better. Mining sites reach lower figures than office data centers because ASICs accept warm intake air.

Does PUE change my hosting bill?

Not when you are billed per kilowatt-hour at the machine: the overhead is then inside the rate.

Can PUE be below 1.0?

No. The site cannot use less than the machines inside it do. Heat reuse is credited under a separate measure.

Does a better PUE make my miner faster?

No. It means less electricity is spent around the machine for the same hashing.