Hardware and cooling
Air cooling
Air cooling removes a miner's heat with built-in fans that pull room air through the machine.
- Heat per kW
- 3,412 BTU per hour
- Airflow needed
- Set by watts and temperature rise
- Direction
- In at the front, out at the back
- Fan power
- Follows the cube of fan speed
- Typical noise at full speed
- About 75 dB or more
What it means in practice
It is the standard design for most machines and needs no extra plumbing, but it is loud and depends on a supply of cool, clean air. Hot intake air reduces hashrate or triggers shutdowns, and dust builds up over time. Air-cooled sites manage hot and cold aisles to keep intake temperatures down.
Setting up an air-cooled miner well
Give it cool air at the front and a clear way out at the back, and keep the two apart. A duct or a board between intake and exhaust is often worth more than another fan. Clean the intake and fans on a schedule; dust is a blanket on the heat sinks.
The machine does the rest: fans speed up as chips warm, and the firmware slows or stops hashing before anything is harmed.
How much air a machine needs
Air carries heat by getting warmer. Decide how many degrees it may rise on the way through, and the flow follows. In metric units, cubic meters per hour are about three times the watts divided by the rise in °C. In US units, cubic feet per minute are 3.16 times the watts divided by the rise in °F.
Example figures: 3,500 W with a rise of 15 °C (27 °F) needs about 3 × 3,500 / 15 = 700 cubic meters per hour, or 410 CFM. With a rise of 10 °C it needs half as much again. For a room, add up all machines and make sure the openings can pass that flow in and out.
Hot air that comes back
The commonest problem is not too little air but the same air twice. Exhaust curls around the machine and enters the front again, warmer each time. The room thermometer may read 25 °C while the intake reads 38.
Measure at the fan grille and not in the middle of the room. If the two differ by more than a few degrees, close the gaps beside and above the machines with boards, and give the hot side its own way outdoors.
An extract fan should move a little more than the machines do together. Then air leaks inward through small gaps, and the hot side cannot push back.
Fans, speed and noise
Airflow rises in step with fan speed, but the power to spin it rises with the cube. At 80% speed a fan moves 80% of the air on about half the power, and is roughly 5 dB quieter.
That is why one degree cooler at the intake is worth having. The firmware lets the fans relax, and the watts saved count every hour. It is also why a duct that chokes the exhaust is costly: the fans race to overcome it.
Dust, altitude and damp
Filters keep dust out and slow the air, so size them generously and change them before they clog. Without filters, plan a blow-out every one to three months, with the machine off and the fan blades held still.
Thin air carries less heat. At 1,500 meters (about 5,000 feet) it is around 15% less dense, and the same fan cools proportionally less. Dry air brings static, damp air brings corrosion. Most makers give a humidity range without condensation; stay inside it and avoid bringing a cold machine into a warm, damp room and switching it on at once.
Worked example
A 3,500 W air-cooled miner turns nearly all its power into heat, about 3,500 × 3.412 ≈ 11,942 BTU per hour, which the room's ventilation must carry away.
Example figures, not live data.
Step by step
- Add up the watts and work out the airflow.
- Size intake and exhaust openings for that flow.
- Separate the hot side from the cold side.
- Measure the temperature at the intake grille after an hour.
- Set a date for the next cleaning.
Common mistakes
- Cooling the room with a machine that only stirs the same warm air.
- Placing the intake of one row in the exhaust of another.
- Running a fan bearing until it screams; a swap takes minutes.
Common questions
What temperature is best for an air-cooled miner?
Cool and steady intake air inside the range on the product page. Fans slow down in cool air, which also cuts noise and power.
Do I need air conditioning?
Usually not. Moving enough outside air through the room does the job for a fraction of the power.
Can an air-cooled miner run outdoors?
Under a roof with dust and rain kept out, yes, as in a ventilated container or shed. It is not weatherproof by itself.
How far can I duct the exhaust?
Short, straight and wide is best. Long runs need an inline fan, because the miner’s own fans are not made to push against resistance.