Hardware and cooling

Airflow (CFM)

Airflow is the volume of air moving through a miner or a room, often given in cubic feet per minute (CFM).

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Units
CFM or cubic meters per hour
1 CFM
about 1.7 m³/h
Pushes against
static pressure
Goes
cool side to hot side, one way
Falls with
dust, long ducts, altitude

What it means in practice

An air-cooled miner pulls cool air in at the front and pushes hot air out at the back. The room must bring in as much cool air as all the miners move and send the hot air away, or the hot air loops back to the intakes and the miners overheat.

How much air a miner needs

A handy rule at sea level: CFM = watts × 3.16 ÷ the temperature rise you accept in °F. A 3,500 W machine with a rise of 30 °F between intake and exhaust needs about 370 CFM. In metric units, cubic meters per hour = watts × 3 ÷ the rise in °C.

The room has to pass the same volume. A duct or window that is too small makes the fans work harder without moving more air.

Free air and real air

The number on a fan’s box is free air: nothing in front, nothing behind. Every filter, grille, duct and heat sink pushes back, and that pushing back is static pressure. A fan has a curve that shows how the flow falls as the pressure rises.

Axial fans, the flat kind, move a lot against little resistance. Centrifugal fans move less and keep going against more. A long duct with two bends wants the second kind, or a much wider pipe.

Openings for a row of machines

Air should enter slowly, because fast air whistles and drags in dust and rain. Example figures: ten machines of 370 CFM need 3,700 CFM. At 500 feet a minute through the opening that is 3,700 ÷ 500 = 7.4 square feet of free area.

A louver with a screen may be only half open, so the hole in the wall becomes about 15 square feet. The outlet needs at least the same. Rooms that overheat usually have strong fans and a small intake.

Place the two on opposite sides of the building where you can. If both must be on the same wall, keep them well apart and put the outlet on the side the wind blows toward, or the warm air comes straight back in.

Pressure in the room

If the exhaust fans move more than comes in, the room is under negative pressure. Doors are hard to open, and air enters through every gap, unfiltered. If the supply side moves more, air leaves through the gaps and dust stays out.

A slight push into the cold side is the aim, with the miners’ own fans doing the last part. A strip of paper at the door tells you which way the air goes.

Corrections that are often left out

The rule CFM = watts × 3.16 ÷ rise holds for air at sea level. At 5,000 feet divide the result by 0.83. Example figures: 370 CFM becomes about 446.

A filter that is half blocked can double its resistance. Note the pressure across it when new, with a simple gauge, and change it when the reading doubles. Watching the gauge is better than watching the calendar.

Fans age as well. A bearing that has run for three years turns slower at the same setting.

Step by step

  1. Add up the watts in the room.
  2. Choose the temperature rise you accept and work out the airflow.
  3. Size the intake and outlet openings from that figure.
  4. Close every path from the hot side to the cold side.
  5. Measure the intake temperature after an hour at full load.

Common mistakes

  • Adding a second fan in line and expecting twice the flow.
  • Reducing a 6-inch outlet to a 4-inch hose.
  • Pointing a household fan at the machines, which stirs warm air instead of removing it.

Common questions

What is hot air recirculation?

Exhaust air finding its way back to the intake. The miner then breathes air it has already heated. A barrier between the two sides fixes it.

How do I size a duct for a miner?

At least as wide as the fan opening, short and with few bends.

What filter should I use?

A coarse washable filter stops most dust with little resistance. Fine filters need several times the area to pass the same air.

Should warm air leave at the top?

It helps, since warm air rises. For machines with strong fans the straight path out of the back matters more.

How do I measure CFM without special tools?

Measure the temperature rise from intake to exhaust and the watts, and turn the rule around: CFM = watts × 3.16 ÷ rise in °F.