Hardware and cooling
Ambient temperature
Ambient temperature is the temperature of the air around a miner, which for an air-cooled miner is the air it breathes in.
- Measured at
- the machine’s intake
- Affects
- chip temperature, fan speed, noise, power
- Upper limit
- on each model’s specification
- Also matters
- altitude and humidity
What it means in practice
Air-cooled miners are designed for intake air within a set range; hotter air means hotter chips, louder fans and, past a limit, lower hashrate or a protective shutdown. Makers list the operating range in each model's specifications, and our setup guides show it for every model.
Measure it where it counts
The number that matters is the air entering the machine, not the weather. Put a thermometer at the intake after the machine has run for an hour: in a closed room it can sit many degrees above the outside air because the exhaust comes back.
Cold air is welcome, with two limits: stay above the maker’s lower figure at start-up, and avoid condensation when a cold machine meets warm, damp air.
The ladder from air to chip
Heat flows from the chip to the heat sink and into the passing air. Each step needs a difference in temperature. At a given fan speed the distance from intake air to chip stays roughly the same, so every degree outside is a degree at the chip.
Example figures: intake 25 °C, chip 70 °C, so the ladder is 45 degrees high. At 35 °C intake the chip would be at 80. The firmware prefers 70, so it raises the fan speed, and only when the fans are at their limit does it lower the frequency.
Hot air that finds its way back
A small leak has a large effect. Example figures: room air of 25 °C mixed with 20% exhaust of 45 °C gives 0.8 × 25 + 0.2 × 45 = 29 °C at the intake. Four degrees are gone without any change in the weather.
You find it with two thermometers, one at the intake and one in the fresh air supply. If they differ by more than two or three degrees, look for gaps beside the machines and above the rack.
Thin air and damp air
At altitude each cubic foot of air holds less mass and carries less heat. At 5,000 feet the density is about 83% of that at sea level, so the same fans cool about a sixth less. Makers often state a maximum altitude or lower the allowed temperature for high places.
Humid air cools almost as well as dry air. The risk is water on cold metal. A machine carried from a cold van into a warm room should stand for a few hours before it is switched on.
Planning by the hottest hours
An average of 15 °C says nothing about the afternoon of 38. Look up the hours above your machine’s limit in a normal year. If there are forty, a lower power mode on those afternoons is enough. If there are a thousand, you need cooled air, water cooling or another place.
Evaporative walls work well in dry regions, where they can take more than 10 °C off the intake air, and do little in humid ones. The same machine can be easy in one state and difficult in the next.
Common mistakes
- Reading the chip temperature and calling it the ambient temperature.
- Putting the thermometer in the sun or in the exhaust stream.
- Starting a machine at minus 20 °C when the manual asks for zero or more.
Common questions
Does heat reduce hashrate?
Past a limit, yes. The firmware lowers frequency to protect the chips, so cooler air can mean more hashrate as well as less noise.
Can a miner run outdoors?
In a weatherproof enclosure with filtered air and the temperature inside its range, yes. Open to rain or dust, no.
What is the best intake temperature?
A range around 10 to 25 °C suits most air-cooled machines: cool enough for slow fans and well above freezing.
Does an air conditioner make sense?
Seldom. Removing 3.5 kW of heat takes roughly another kilowatt. Moving outside air through the room is cheaper in most climates.
Does power rise with temperature?
A little. Warm chips leak more current and fans work harder, so a hot day can add a few percent to the same hashrate.