Hardware and cooling
Dry cooler
A dry cooler is an outdoor radiator with fans that cools the liquid coming back from hydro or immersion miners.
- Moves heat to
- outside air
- Uses water
- no, the loop is closed
- Limited by
- the outdoor dry-bulb temperature
- Key figure
- approach: coolant out minus air in
- Moving parts
- fans and one pump
What it means in practice
Warm coolant flows through the dry cooler's fins and fans blow outside air across them, so no water is used up. The colder the outside air, the cooler the liquid returns to the miners. Dry coolers are sized by how many kilowatts of heat they can remove at a given outdoor temperature.
How a dry cooler is sized
Start with the heat: nearly all the machines’ kilowatts. Then the hottest outdoor day, and the warmest coolant the machines accept. The gap between the two decides the size: a wider gap needs a smaller cooler.
That is why miners that accept warm inlet water are easy to cool: the cooler still works on a hot afternoon.
Flow and temperature in the loop
The heat, the flow and the temperature difference belong together. Example figures: 200 kW of miners, water, and a difference of 8 °C between the warm and the cool pipe. 200 ÷ (4.186 × 8) = 5.97 liters a second, about 358 liters a minute.
Halve the difference and the flow must double, which needs bigger pipes and a stronger pump. Makers of hydro machines state the flow and pressure they want, so start there and let the temperatures follow. A glycol mix carries a little less heat than water and needs about 5 to 15% more flow.
Approach, the number that sells coolers
Approach is how close the coolant gets to the outdoor temperature. Example figures: air 35 °C and coolant leaving at 43 °C means an approach of 8 °C. If the machines accept 45 °C water, there are 2 °C to spare on that afternoon.
Asking for 4 °C instead of 8 can nearly double the coil. So the maximum inlet temperature of the machines is worth more than any option on the cooler. Compare coolers at the same capacity, air temperature, approach and flow, or the figures mean nothing.
What the fans cost
Fan power falls with the cube of the speed. Example figures: a cooler with 6 kW of fans at full speed uses 6 × 0.6³ = 1.3 kW at 60%. For most hours of the year the air is cool enough for that.
A controller that slows all fans together beats one that switches some off. The saving goes straight into the overhead, and the noise drops as well: a good reason to choose a cooler one size larger near neighbors.
Placing and maintaining it
A cooler breathes. Walls, another cooler’s exhaust or a roof edge can feed it its own warm air. Leave the distances in the manual, and let the hot side blow where the wind carries it away.
Pollen and dust block the fins from the outside, and a soft wash in spring and autumn restores them. Inside the loop look after pressure, filters, the glycol share and the corrosion inhibitor. The machines’ narrow channels are the first to suffer from dirty water.
Write the readings into a log each month. A slow drift is seen there first.
Common mistakes
- Sizing for the average summer day instead of the hottest one.
- Using plain water where the pipe passes outside in winter.
- Placing two coolers face to face.
Common questions
What is the difference between a dry cooler and a cooling tower?
A cooling tower evaporates water to reach lower temperatures. A dry cooler only moves air past fins, so it uses no water.
Does a dry cooler need antifreeze?
Where it can freeze, the loop runs a water and glycol mix at the share the maker allows.
What is an adiabatic cooler?
A dry cooler with wetted pads in front that cool the air on the hottest days. It uses some water for some hours and is smaller for the same job.
Can one cooler serve several racks?
Yes, with a common loop and balanced flow. Two smaller units give you one spare when the other is being cleaned.
Does it work in freezing weather?
Yes, with glycol. The controller slows or stops fans so the coolant does not become too cold for the machines.