Hardware and cooling

What is hydro cooling?

Hydro cooling circulates liquid through cold plates fixed to a miner's chips and removes the heat outside the machine.

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Coolant
Treated water or a glycol mix
Contact
Cold plates on the chips
Power feed
Usually 380 to 415 V three-phase
Stated by the maker
Flow, pressure and inlet temperature
Heat out
Warm water, ready to reuse

What it means in practice

Hydro miners are built for it, with water inlets and outlets instead of fans, and usually run at higher power and hashrate than air models. They are mounted in racks or containers connected to dry coolers or cooling towers. Many hydro models need 380 to 415 V three-phase power rather than the 220 to 240 V used by most air-cooled units.

What the loop needs

Hydro miners have cold plates on the chips and hose connections for coolant in and out. A pump sends treated water or a glycol mix through them at the flow the maker states, the warm water goes to a dry cooler or a heating system, and comes back below the inlet limit. Most hydro machines run on three-phase power.

Flow and temperature rise

Water takes 4.19 kilojoules to warm one liter by one degree. So the flow in liters per second is the kilowatts divided by 4.19 and by the rise.

Example figures: a 5.5 kW machine with a rise of 8 °C needs 5.5 / (4.19 × 8) = 0.164 liters per second, about 9.8 liters a minute. Ten machines need 98. A glycol mix carries a little less heat, so allow around 10% more flow. The maker’s minimum flow wins over your own calculation.

Water quality is a running task

The passages in a cold plate are narrow. Scale, rust and algae narrow them further, and one blocked plate shows as one hot board. Makers state limits for hardness, acidity and conductivity, and recommend treated or deionized water with an inhibitor.

Mixing metals matters. Copper and aluminum in the same loop corrode each other unless the coolant is made for it. A filter at the inlet, a water test every few months and a log of both keep a loop healthy for years.

Too cold is also a problem

Cold pipes sweat in warm, damp air, and water on a board is worse than heat. Keep the coolant above the dew point of the room.

Example figures: air at 30 °C with 60% humidity has a dew point near 21 °C. A loop at 18 °C would drip; one at 25 °C would not. In winter a mixing valve sends part of the warm water straight around, so the inlet stays within the range on the data sheet.

The electrical side

Three-phase power spreads the load over three wires. Example figures: 5,500 W on 400 V three-phase at a power factor of 0.98 draws 5,500 / (1.732 × 400 × 0.98) = 8.1 A per phase. The same power on 240 V single-phase would be 22.9 A.

In North America the usual three-phase voltages are 208 and 480 V, so a site often needs a transformer that delivers 400 or 415 V. Ask for the input range on the machine’s label before you plan the panel.

Alarms that protect the loop

Flow switches, pressure gauges, leak sensors and a level sensor in the header tank belong on every loop. The controller should stop the machines when flow stops, because a cold plate without flow overheats in seconds.

Quick couplings with valves let one machine come out while the others run. Wipe, cap and label the ends.

Worked example

A rack of 10 hydro units at 5,500 W each needs cooling capacity for 10 × 5.5 = 55 kW, plus a margin for warm days.

Example figures, not live data.

Step by step

  1. Add up the kilowatts and the maker’s minimum flow.
  2. Size pump and dry cooler for your hottest day.
  3. Flush and pressure-test the loop before connecting machines.
  4. Fill with the specified coolant and bleed the air.
  5. Start the machines one by one and watch flow and inlet temperature.

Common mistakes

  • Filling a loop with untreated tap water.
  • Running the loop below the dew point of the room.
  • Ordering for a 208 V panel when the machine needs 380 to 415 V.

Common questions

Are hydro miners more efficient?

Usually a little, because chips held at a steady, lower temperature need less voltage for the same speed. The bigger gain is hashrate per machine and far less noise.

Can I run a hydro miner at home?

Yes, with a suitable power feed and somewhere for the heat to go, such as a small dry cooler or a heating system. Some home hydro units run on single-phase power.

How warm is the water that comes out?

A few degrees above the inlet, often 40 to 60 °C depending on the model and how you run it.

What is the difference between hydro and immersion?

In hydro, water flows through sealed plates. In immersion, the whole board sits in a non-conductive fluid.