Three-phase power

Three-phase power delivers electricity over three conductors whose voltages peak at evenly spaced times, giving more power per wire than single-phase.

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Live conductors
three
Phase shift
120 degrees apart
Line to neutral
line voltage ÷ √3
Forms
wye (with neutral) and delta
Main benefit
more power through the same copper

What it means in practice

Industrial sites and mining containers use it because it carries large loads efficiently and smoothly. A common mining arrangement is 415Y/240 V, where each phase-to-neutral leg supplies 240 V to single-phase miners while some hydro machines connect across phases at 380 to 415 V. Power on a balanced three-phase load is √3 × line voltage × current × power factor.

When a miner needs three-phase power

Full-size air-cooled machines mostly take single-phase power at 200 to 240 V. Many water-cooled and rack machines from about 5 kW up ask for three-phase power at 380 to 415 V, because the same power then needs thinner cable and smaller breakers.

Homes in much of Europe have a three-phase supply; homes in the US rarely do. Commercial and industrial sites usually have it in both.

Wye and delta in plain words

In a wye supply the three windings meet in one point, and that point is the neutral. You get two voltages: the higher one between phases and the lower one from a phase to neutral. 415 and 240 V belong together, as do 400 and 230, 480 and 277, and 208 and 120.

In a delta supply the windings form a triangle. There is one main voltage between phases and usually no neutral. A site with 240 V delta feeds 240 V miners between phases. A site with 480 V delta needs a transformer first.

Why the neutral can stay almost empty

The three currents peak one after another. When all three are equal they cancel out in the neutral. When they differ, the neutral carries the difference.

Example figures: ten machines of 14.6 A on a 415/240 V supply, split four, three and three. The phases carry 58.4, 43.8 and 43.8 A. The neutral carries about 14.6 A, the current of the one extra machine. Twelve machines, four on each phase, leave it near zero.

Balance also decides what the main breaker sees. It trips on its most loaded phase, so a badly spread room runs out of capacity early.

Saving copper, in numbers

Example figures for 30 kW. On single-phase 240 V the current is 30,000 ÷ 240 = 125 A in two conductors. On 415 V three-phase it is 30,000 ÷ (√3 × 415) = 41.7 A in three. One third of the current means thinner cable, smaller plugs and less heat in every joint.

This is why containers and hydro racks are built for it. The cable for a large single-phase feed would be too stiff to bend behind a rack.

Reading a three-phase machine’s label

Look for the voltage range, the current per phase, whether a neutral is needed, and the connector. A line such as “380–415 V 3~ 12 A” means three live conductors and 12 A in each. Some models are wired with neutral and some without, and the wrong one will not start.

A power meter that clamps around one conductor shows one phase. Read all three. Equal values mean the machine is healthy. A phase at zero means a lost fuse or a loose terminal, and a licensed electrician should look at it before the machine runs again.

Worked example

A hydro miner on 415 V three-phase drawing 12 A per phase at a power factor of 1 uses √3 × 415 × 12 ≈ 8,626 W.

Example figures, not live data.

Common mistakes

  • Multiplying volts by amps by three instead of by √3 when the voltage is the one between phases.
  • Assuming any industrial three-phase outlet fits: 208, 400 and 480 V outlets can look alike.
  • Connecting all single-phase machines to the phase nearest the door.

Common questions

Can I run a three-phase miner at home?

Only with a three-phase supply at the right voltage. An electrician can tell you what your connection offers; otherwise choose a single-phase model or host the machine.

Can single-phase miners run on a three-phase supply?

Yes. They are spread evenly, each between one phase and neutral, or between two phases, depending on the voltage.

What is a phase converter, and does it help?

It makes a third phase from a single-phase line, mostly for workshop motors. For a miner it adds cost and losses, so a single-phase model is the better match.

How do I know if a building has three-phase power?

Look at the main breaker: three linked poles are a strong sign. The utility or an electrician can confirm the voltage and the available current.

Does phase rotation matter to a miner?

Not to the electronics. It matters to three-phase pump and fan motors, which run backward when two phases are swapped.