Power and wiring
Breaker sizing
Breaker sizing means choosing a circuit breaker and wiring that can carry a miner's current continuously without tripping or overheating.
- Breaker protects
- the cable
- Load that never stops
- count 125% of its current (US practice)
- US copper, common pairs
- 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A
- 240 V in the US
- a two-pole breaker
- Work done by
- a licensed electrician
What it means in practice
Miners draw their full current for hours on end. US electrical practice treats that as a continuous load, which should not exceed 80 percent of the breaker's rating. Work out the current from the miner's power and voltage, then pick the breaker, wire gauge and plug to match, and have an electrician do the work.
The 125% rule step by step
Find the current: watts ÷ volts. Multiply by 1.25 for a load that runs around the clock. Take the next breaker size up, and use cable rated for that breaker. Use the highest power the maker states, with its tolerance, not the typical figure.
One machine per breaker keeps a fault on one machine from stopping the others and makes a restart simple.
What a breaker protects
A breaker is there for the wire in the wall. It opens when the current would heat the cable beyond what its insulation can stand. It does not look after the miner, which has its own protection in the power supply.
This is why the order of choice is fixed: first the load, then the breaker, then a cable that suits the breaker. Swapping in a bigger breaker because the old one trips turns that around and leaves the cable unprotected.
The same machine at two voltages
Example figures: 5,500 W. At 240 V it draws 22.9 A. Times 1.25 is 28.6 A, so a 30 A breaker with 10-gauge copper. At 208 V it draws 26.4 A. Times 1.25 is 33.1 A, so the next size is 35 A and the cable grows with it.
Voltage is therefore the first question an electrician asks. The second is the length of the run, because a long cable is often made one size thicker to keep the voltage up.
Room in the whole panel
A circuit can be right while the panel is full. Example figures: a 200 A home service at 240 V. Two machines at 14.6 A add 29.2 A that never goes away. If the house already reaches 120 A on a winter evening with heat and an oven, about 50 A are left. With an electric car on the charger they may not be.
Electricians do a load calculation for this. They add up what is installed with factors from the code. It takes an hour and answers the question for good.
How breakers trip
There are two parts inside. A strip of metal bends slowly with heat and reacts to a lasting overload in minutes or hours. A coil reacts to a short circuit in milliseconds.
Power supplies draw a brief rush of current when they are switched on. Ten machines on one switch can trip the coil although each is fine alone. Starting them a few seconds apart solves it. Warm panels also trip earlier, since the heat of neighboring breakers adds up.
A breaker that has tripped many times, or under a short circuit, may no longer trip where it should. Electricians replace such a breaker instead of resetting it once more.
Worked example
A 3,500 W miner on 240 V draws about 14.6 A, so on an 80 percent rule it needs a circuit of at least 20 A.
Example figures, not live data.
Step by step
- Take the highest watts the maker states and the voltage measured on site.
- Divide to get amps and multiply by 1.25.
- Choose the next standard breaker size.
- Match cable, receptacle and cord to that breaker.
- Have the panel’s total load checked and the work done by an electrician.
Common mistakes
- Fitting a 30 A breaker on 12-gauge cable to stop it tripping.
- Calculating with the low-power mode and later switching the machine to full power.
- Sharing the miner’s circuit with a freezer or tools.
Common questions
What breaker does a 3,500 W miner need?
At 240 V it draws 14.6 A. Times 1.25 is 18.2 A, so a 20 A breaker.
Why does the breaker trip after an hour?
A breaker near its limit warms up slowly and trips on heat, not at once. The circuit is too small for a load that never pauses.
Are there breakers rated for 100% load?
Yes, mostly larger ones in approved enclosures. Ordinary household breakers are planned at 80% for a load that never stops.
Do I need a GFCI breaker?
Rules depend on the room and the country. Power supplies leak a tiny current through their filters, and several on one device can trip it, so ask the electrician how to divide them.
Does the 125% rule apply in Europe?
The codes are written differently, with the same thought behind them. A 16 A circuit is not meant to carry 16 A day and night, so a full-size machine usually gets a larger circuit of its own.