Power and wiring

Transformer (kVA rating)

A transformer steps utility voltage down to the voltage miners use, and its kVA rating states how much load it can carry.

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Rating means
apparent power it can carry
Full-load current (three-phase)
kVA × 1,000 ÷ (√3 × volts)
Also on the nameplate
impedance, voltages, taps, cooling class
Losses
core (always) and winding (with load)
Cooled by
oil or air

What it means in practice

Mining sites typically use pad-mounted units that take medium-voltage utility power and output a voltage such as 415Y/240 V. Because miners run near full load all day, planners keep load at or below about 80% of the transformer's rated kVA. Transformer lead times can be long, so they shape how quickly a site can grow.

From kVA to machines

kVA times power factor gives kilowatts. Modern miner power supplies sit close to a power factor of 1, so a 2,500 kVA unit held at 80% carries about 2,000 kW: roughly 570 machines of 3.5 kW.

The order in which a site is built follows from this: the utility connection first, the transformer next, then switchgear, cooling and machines.

What the nameplate tells you

Beside the kVA you find the two voltages, the connection of the windings, the impedance in percent, the weight and a cooling class. A class such as ONAN means oil moved by natural flow and cooled by natural air. ONAF adds fans and brings a second, higher rating.

Taps let an electrician shift the output by a few percent to match the utility’s real voltage. If every machine in a container reads 250 V at night, the tap setting is the first thing to look at.

From the rating to amps and fault current

Example figures: 2,500 kVA with 415 V output. Full-load current is 2,500,000 ÷ (√3 × 415) = about 3,478 A. At 80% it is about 2,780 A, and that is what the busbars and main breaker carry day and night.

Impedance decides what happens in a short circuit. With 5.75%, the current can reach about 3,478 ÷ 0.0575 = 60,500 A for an instant. Breakers and panels behind the transformer need an interrupting rating above that, which is why the engineer asks for the impedance before ordering them.

Why mining is hard on a transformer

A town’s transformer rests at night. A miner’s never does. The oil and the windings settle at their highest temperature and stay there, and insulation ages faster when hot. An old rule of thumb says each 6 to 8 °C more halves its life.

Power supplies also draw a current that is not a perfect wave. The extra frequencies, called harmonics, warm the windings and the neutral. Designs made for such loads carry a K-factor or a harmonic rating. This is the reason for the 80% habit, together with hot summer afternoons.

Losses on the bill

A good unit loses about 1% of what passes through. It sounds small. Example figures: 2,000 kW through a transformer with 1% loss is 20 kW. Over 730 hours that is 14,600 kWh a month.

Whether the owner of the site or the customers carry that depends on where the meter sits. If the utility measures at high voltage, the loss is inside the bill. If each machine is metered at its outlet, it is part of the site’s overhead.

Core losses run even when no machine is on. They are the price of keeping the transformer ready.

Worked example

A 1,500 kVA transformer loaded to 80% carries about 1,500 × 0.8 = 1,200 kVA, roughly 1,200 kW at a power factor of 1, enough for about 1,200 / 3.5 ≈ 342 machines at 3,500 W.

Example figures, not live data.

Common mistakes

  • Choosing by the price per kVA and forgetting the output voltage the machines need.
  • Running at 100% of the rating because the first winter went well.
  • Ordering the machines before the transformer has a delivery date.

Common questions

What is the difference between kVA and kW?

kVA is the total load a transformer carries; kW is the part that does work. The two are equal at a power factor of 1.

What secondary voltage do mining transformers use?

Often 415Y/240 V, which gives 240 V from each phase to neutral for single-phase machines and 415 V between phases for three-phase ones.

Can two transformers share one load?

Yes, if their voltages, connection and impedance match closely. Otherwise one takes more than its share. An engineer should decide that.

What do the taps do?

They change the number of active turns in small steps, so the output can be corrected when the utility’s voltage sits high or low.

Does a home miner need a transformer?

Not a separate one. The utility’s transformer already supplies the house. Only machines that need a voltage the building does not have would require one.