Power and wiring
C13/C14 connector
C13 and C14 are the standard medium-current appliance connectors in IEC 60320, familiar from desktop computer and monitor cords.
- Standard
- IEC 60320
- IEC rating
- 10 A, 250 V
- North American rating
- up to 15 A
- Pin temperature rating
- 70 °C
- Seen on
- computers, monitors, switches, small miners
What it means in practice
They are rated 10 A under IEC and up to 15 A under UL ratings, which suits small home miners, controllers and network gear but not most full-size ASICs. Some PDUs mix C13 and C19 outlets so that switches and small devices can share a rack with miners. Using a C13 cord on a load beyond its rating risks overheating.
Where the pair is used in mining
The C13 is the end of the cord with holes; the C14 is the inlet with pins. Home miners, desk heaters, switches and monitors use it. A quick check is the current: watts ÷ volts has to stay under the cord’s own rating, and well under it for a machine that never stops.
The cord matters more than the connector
The same C13 end is molded onto very different cables. The thin cord that came with a monitor is often 18 AWG and marked 10 A. A 16 AWG cord is usually marked 13 A and a 14 AWG one 15 A. All three fit the same inlet.
A desktop computer uses its full power for minutes. A miner uses it for months. Take the marked figure, leave a fifth of it free, and keep the thin monitor cords for monitors.
What it can carry at each voltage
The connector is limited in amps, so the watts depend on the supply. Example figures with 10 A: 1,200 W at 120 V, 2,300 W at 230 V and 2,400 W at 240 V. With a fifth kept free for a load that never stops it becomes 960, 1,840 and 1,920 W.
This explains why a 1,000 W home miner is fine on one cord everywhere, while a 1,800 W model belongs on 230 or 240 V. On 120 V that machine would need 15 A, more than a normal household circuit should carry all day.
Near relatives that look alike
The C15 looks like a C13 with a notch. It is made for hot inlets, and a C15 cord fits a C14 inlet as well. The other way round does not work: a C13 will not go into a C16 inlet, which keeps a cool cord away from a hot device.
The C5, the cloverleaf on laptop supplies, and the C7, the figure eight, carry only 2.5 A. Small desk miners often avoid all of these and use a low-voltage barrel plug or USB-C instead.
Two C13 cords on one machine
Several full-size machines of recent years have a power supply with two C14 inlets. Each feeds half of the supply, so each cord stays near 7 or 8 A at 240 V. Example figures: 3,400 W ÷ 240 V = 14.2 A, divided by two = 7.1 A per cord.
Both inlets must see the same phase and circuit arrangement the maker describes. Where a PDU has separate groups, put both cords of one machine into the same group unless the manual allows otherwise, and count the whole 14.2 A against that group.
Worked example
A small home miner drawing 1,200 W at 120 V pulls 1,200 / 120 = 10 A, which is at the C13's IEC rating and within its 15 A UL rating.
Example figures, not live data.
Common mistakes
- Taking a cord from the drawer without reading the gauge printed on it.
- Using a splitter that turns one C14 into two C13 outlets for a second miner.
- Assuming a 15 A marking in North America also counts as 15 A under IEC rules.
Common questions
Can a C13 cord power a full-size ASIC?
Most need C19 cords or two cords side by side. Use the connector the maker names, one cord per inlet.
Does a C13 plug fit a C20 inlet?
No. The larger pair has rectangular pins in a different layout, so the two cannot be mixed by mistake.
Is C13 the same as a kettle plug?
People call it that, but a kettle uses the notched C15, which stands more heat.
Can I use a C13 cord on a 240 V circuit?
Yes. The connector is rated for 250 V. The other end has to match the wall or PDU, such as NEMA 6-15 or C14.
What should I do if the plug feels hot?
Stop the machine, let it cool, and replace the cord. If the inlet is discolored, have the power supply checked before it runs again.