Power and wiring

C19/C20 connector

C19 and C20 are the high-current appliance connectors defined in IEC 60320, used on many miner power cords and mining PDUs.

Put it to work Hosting versus home Running a machine at home against hosting it. Open the page
Standard
IEC 60320
IEC rating
16 A, 250 V
North American rating
up to 20 A
Shape
three flat pins in a rectangular body
Cord end
C19 (sockets)
Machine or PDU side
C20 (pins)

What it means in practice

The C19 is the socket on the cord and the C20 is the inlet on the device or PDU outlet. They are rated 16 A under IEC and up to 20 A under North American UL ratings, against 10 A and up to 15 A for the smaller C13/C14 pair. That extra headroom is why they appear on servers, rack PDUs and miners drawing several kilowatts.

How to choose a C19 cord

Look at four things: the plug at the wall or PDU end (C20, NEMA 6-20, NEMA L6-30, Schuko and others), the wire gauge, the current rating and the length. Thicker wire has a lower gauge number: 12 AWG carries more than 14 AWG.

Short cords of the right gauge run cooler. A cord that is warm to the touch after an hour is a sign to go one size up.

Reading the code on a power cord

A cord has two ends and often two names, for example “C19 to L6-30P” or “C19 to C20”. The first part goes into the machine. The second goes into the wall or PDU. Between them the cable itself is printed with its gauge and type, such as 12 AWG and SJT.

The weakest of the three decides what the cord may carry. A C19 end on 14-gauge wire with a 15 A plug is a 15 A cord, however large the connector looks. The printed rating on the plug and the wire is worth reading before the first start.

Odd and even numbers

In this family the odd number is the part with holes and the next even number is the part with pins. C13 goes with C14, C15 with C16, C19 with C20 and C21 with C22. The holes are always on the side that carries the voltage, so you can never touch a live pin.

That also tells you which way round a jumper cord goes. The C20 end fits into the PDU’s C19 outlet and the C19 end goes into the miner’s C20 inlet. People often call the outlet on a PDU a C20, which leads to the wrong cord in the basket.

Heat at the contact

Current itself is rarely the trouble. A loose contact is. Example figures: a contact with a resistance of 10 milliohm at 15 A turns 15 × 15 × 0.01 = 2.25 W into heat in a spot the size of a fingernail. A clean one with 1 milliohm makes 0.2 W.

So push each plug fully home, use cords with a locking end where the machine vibrates, and replace any cord whose plastic has turned brown or hard. Do not clean a burnt pin and carry on, because the spring in the mating part has lost its force as well.

One inlet or two

A machine above roughly 3,800 W at 240 V passes 16 A, the IEC figure for one inlet. Makers then fit two inlets, or use a different connector, or go to three-phase power. With two inlets the load divides between them, though not always equally.

Example figures: 5,500 W at 240 V is 22.9 A, or about 11.5 A for each of two cords. Both cords belong on circuits the electrician has planned for the pair. A machine that starts with one cord plugged in is still not allowed to run that way unless the manual says so.

Worked example

A 3,500 W miner at 240 V draws about 14.6 A, which is 14.6 / 20 ≈ 73% of a C19's 20 A UL rating and above a C13's 10 A IEC rating.

Example figures, not live data.

Common mistakes

  • Buying by connector name alone and finding the far end does not fit the wall.
  • Plugging both cords of one machine into the same small circuit.
  • Using a long cord coiled in a tight bundle, where its heat cannot escape.

Common questions

Why do some miners have two C19 inlets?

Their power supply splits the load over two cords so each stays inside its rating. Both must be plugged in, on circuits that can carry them.

What is the difference between C19 and C20?

C19 is the socket on the cord, C20 the inlet with pins on the machine or PDU.

Is C21 the same as C19?

It has the same shape with a higher temperature rating, and a C21 cord also fits a C20 inlet. It is made for equipment whose inlet runs hot.

How long may a C19 cord be?

As short as reaches comfortably. Two meters, about six feet, is common. Longer cords need thicker wire for the same current.

Do miners come with power cords?

Often not, because plugs differ by country. The box contents on the product page tell you.